[X] [X][X][X][X][X][X][X][X][X][X][X][X][X][X][X][X][X][X][X]TSN(Z) 160-630/10(6) N3 - Dry-type transformers with the air barrier insulation
[X][X][X][X][X][X][X][X][X][X][X][X][X][X][X][X][X][X][X][X][X][X][X][X][X][X][X][X][X]

TSN(Z) 160-630/10(6) N3

Transformers with air-barrier insulation aramid paper
TSN 250/10(6) N3
Winding TSN
Заглушка
Equipment request
Models for delivery:
TSN 160/10(6) N3
TSNZ 160/10(6) N3
TSN 250/10(6) N3
TSNZ 250/10(6) N3
TSN 400/10(6) N3
TSNZ 400/10(6) N3
TSN 630/10(6) N3
TSNZ 630/10(6) N3
Producer
"KTZ" JSC
[X][X][X]


1. General characteristics:

Power range
25-2500 kVA
Winding connection
D/Yn-11, Y/Yn-0
Voltage HV winding
6, 10 kV
Voltage LV winding
0,4 kV
Unprotected execution (type TSN)
degree of protection IР-00
Protected execution (type TSNZ)
degree of protection IР-21
Non-excitation regulating power
±5×2,5%.


2. Assignment:

Three-phase dry-type transformers with air-barrier insulation aramid paper type "Nomex" switching with non-excitation regulating. Designed to convert electrical energy into electric three-phase alternating current with frequency of 50 Hz. Installed in industrial premises and public buildings, which have high requirements in terms of fire safety, explosion-proof, ecological purity.

Transformers are available in the version with degree of protection IP00 (without casing — type TSN) or R (bonnet — type TSNZ). This type transformers do not support combustion and does not emit toxic smoke or dangerous particles. Reduces losses associated with electricity transmission. Transformers can be placed near sources of their load. The voltage regulation of ±5% in steps of 2.5% non-excitation regulating power by moving jumpers.


3. Conditions:

Height over sea level
up to 1000 m
Temperature for temperate climates
from −60°C to +40°C
Thermal class
F
Thermal class of winding
Н
Fire class
F1


4. Working resource:

Operating mode
long
Warranty period
3 years
Full life
not less than 25 years


5. Construction of transformers:

The main insulating material, paper "Nomex", withstands temperatures 220ºС, thus the design of the transformer has a substantial safety margin. Transformers can be used with a temperature of 80°C and load is around 133% of nominal. This will lead to lower costs than the costs associated with installation of an additional transformer.

"Nomex" is a synthetic aromatic polyamide, providing a high level of electrical, chemical and mechanical protection. It helps to increase the service life of the transformer, reducing the number of premature failures, repairs and protects with increasing electrostatic voltage.

The magnetic core is made of high quality electrical steel. Special cutting line of the Italian firm "SOENEN" and methods of blending "Step-Lap", Assembly, applying bandages, tie rods and special adhesives provide low no-load losses and noise. For corrosion protection applied silicon paint.

LV winding made of copper or aluminum wires with insulation "Nomex" or of copper or aluminum foil. As the interlayer insulation paper is used "Nomex".

HV windings are made as a coil, and the layer of wires with insulating paper "Nomex".

Transformers with a casing at the request of the customer are manufactured in the following versions:

  • with the ability to connect power cables through the bottom shell;
  • with tire conclusions HV and LV through the cover and side panel of the transformer.

Protective shell provides access to the transformer via a removable panel on the long side of the transformer. On request of the consumer, the factory can design and manufacture transformers with different parameters of any design. Transformers can be used on objects underground.

 


1. Main advantages:

Dry-type transformers insulated with Nomex have a more compact size than oil-immersed transformers or transformers filled epoxy compound. They are suitable for repair, and if necessary, the repair of dry transformers insulated with "Nomex" is much shorter than that of the transformer with liquid dielectric. Another distinct advantage of this product is its water — resistance and harmless to the environment.

Compared with oil-immersed transformers or transformers filled epoxy compound there are the following advantages:

  • Fire and explosion safety;
  • Suitable for repair
  • Idling losses and short circuit reduced by 10%;
  • Do not contain harmful substances and recycling are easily recyclable;
  • Excellent dielectric pulse characteristics help to improve strength and increase their reliability;
  • Test norms to the applied voltage and pulse surge increased by 25%;
  • Do not contain by-products of decomposition at the operating temperatures of the transformers;
  • Slight ageing of insulation at elevated temperatures can withstand normal and emergency loads over a wider range;
  • Work in conditions of emergency peak load does not lead to the fragility of the dielectric isolation;
  • Cheaper to manufacture.

 


1. Capacity from 160 to 630 kVA:

ModelIdling losses, WShort circuit losses, WVoltage short circuit, %
TSN(Z)-16067017154.0
TSN(Z)-25068019854.0
TSN(Z)-400115038904.0
TSN(Z)-630150064005.5

 


1. TSN type. Without protection. IР-00. Capacity from 160 to 630 kVA:

PowerABHabcc1Weight
160 kVA12706001250550450400260940 kg
250 kVA12906001260550450370300980 kg
400 kVA156085014406706704604601820 kg
630 kVA173085014606706705355352230 kg


2. Taps TSN type capacity from 160 to 630 kVA:

TypeBL2SideS, mm
TSN 160-63030+130+1BH5
TSN 160-25050+125+1НН6
TSN 40050+125+1НН6
TSN 63060+125+1НН10


3. TSNZ type. With protection. IР-21. Capacity from 160 to 250 kVA:

PowerLBHh1bb1dIWeight
160 kVA14758801450175250200122601160 kg
250 kVA14909201460200280210162751195 kg


4. TSNZ type. With protection. IР-21. Capacity from 400 to 630 kVA:

PowerHBLh1h2cIbWeight
400 kVA16709801820155015501006706702085 kg
630 kVA17259801990158015801006706702560 kg


5. Taps TSNZ type capacity from 400 to 630 kVA:

 

Download
pdf
Transformers TSNZ 6(10) kV (383,9 KB)
technical details
[X][X][X][X]
[X]