[X] [X][X][X][X][X][X][X][X][X][X][X][X][X][X][X][X][X][X][X]Transformer TMPN (G) 63-400 6(10) kV
[X][X][X][X][X][X][X][X][X][X][X][X][X][X][X][X][X][X][X][X][X][X][X][X][X][X][X][X][X]

TMPN (G) 6(10) 63-400 N1, N3

Three-phase oil transformers for power submersible pumps for oil production
Transformer TMPN (G) 6(10) 63-400 N1, N3
Equipment request
Models for delivery:
TMPN-63/1 N1, N3
TMPN-100/3 N1, N3
TMPNG-100/3 N1, N3
TMPN-160/3 N1, N3
TMPNG-160/3 N1, N3
TMPN-250/3 N1, N3
TMPNG-250/3 N1, N3
TMPN-400/3 N1, N3
TMPNG-400/3 N1, N3
Producer
"KTZ" JSC
[X][X][X]


1. General characteristics:

Power range
63, 100, 160, 250, 400 kVA
Winding connection
Yn/Y-0
Voltage HV winding
6, 10 kV
Voltage LV winding
0,38 kV
Voltage regulation
HV
Non-excitation regulating power
±2×2,5%
Climatic version
N1, NЗ
Degree of protection
IP13


2. Assignment:

Three-phase double-winding power transformers with non-excitation regulating power. With the option of hermetic performance (TMNPG type). Designed to power submersible electric pumps for oil production. Transformers meet the requirements of GOST 11677 and technical condition 5100 RK 0001 0033 АО-051-2005.

Transformers are not designed to work in the conditions of shaking, vibration, impact, inertial forces, shock, explosive and corrosive environment.


3. Conditions:

Height over sea level
up to 1000 m
The ambient air temperature
from −45°C to +40°C
Relative humidity
no more than 80% when +25°C


4. Working resource:

Warranty period
3 years
Full life
not less than 25 years

 


1. TMPN. Capacity from 63 to 400 kVA:

ТипDegrees number of regulationIdling losses, kWtLoss short circuit, kWtIdling current,%Short-circuit voltage, %
TMPN-63/110 / 200,221,282,25,5
TMPN-100/310 / 5 / 25 / 50,291,971,45,5
TMPN-160/310 / 25 / - / 50,442,651,25,5
TMPN-250/325 / 25 / 25 / 250,613,70,67,0
TMPN-400/325 / 25 / 250,95,81,07,0


2. TMPNG (Hermetic). Capacity from 100 to 400 kVA:

ModelDegrees number of regulationIdling losses, kWtLoss short circuit, kWtIdling current,%Short-circuit voltage, %
TMPNG-160/325 / 250,42,651,25,5
TMPNG-250/325 / 250,653,81,27,0
TMPNG-400/325 / 250,95,81,07,0

 


1. TMPN. Capacity 63 kVA:

PowerL, mmB, mmH, mmA, mmA1, mmOil weight, kgFull weight, kg
63 kVA12005701415500480152500


2. TMPN. Capacity from 100 to 160 kVA:

PowerL, mmB, mmH, mmA, mmA1, mmOil weight, kgFull weight, kg
100 kVA12208001500500480210650
160 kVA13009001600550550254840


3. TMPN. Capacity from 250 to 400 kVA:

PowerL, mmB, mmH, mmA, mmA1, mmOil weight, kgFull weight, kg
250 kVA1470118016605505503401180
400 kVA1344127016006606304181580


4. TMPNG (Hermetic). Capacity 100 kVA:

PowerL, mmB, mmH, mmA, mmA1, mmOil weight, kgFull weight, kg
100 kVA12208001400550480210650


4. TMPNG (Hermetic). Capacity from 250 to 400 kVA:

PowerL, mmB, mmH, mmA, mmA1, mmOil weight, kgFull weight, kg
250 kVA1350112014906606303401180
400 kVA1344127016606606304181580
Download
pdf
Transformers TMPN (G) 6(10) kV (338,3 KB)
technical details
[X][X][X][X]
[X]