Equipment request
Models for delivery: |
---|
TM-1000/35/0,4 N1 |
TM-1600/35/0,4 N1 |
TM-1000/35/6,3/10,5 N1 |
TM-1600/35/6,3/10,5 N1 |
TM-2500/35/6,3/10,5 N1 |
TM-4000/35/6,3/10,5 N1 |
TM-6300/35/6,3/10,5 N1 |
Producer
"KTZ" JSC[X] [X] [X]
[X] [X] [X] [X]
1. General characteristics:
Power range
1000, 1600, 2500, 4000, 6300 kVA
Winding connection
Y/Yn-0; Y/D-11
Voltage HV winding
35 kV
Options voltage LV winding
0,4 / 6,3 / 10,5 kV
Voltage regulation
Non-excitation regulating power HV ±2×2.5%
Climatic version
N1
2. Assignment:
Three-phase double winding oil transformers, with natural oil cooling, with non-excitation regulating power.Designed for operation in transmission systems of electricity, while providing a minimum electrical losses in power lines. The use of a transformer TM type allows to provide the consumer with a reliable power supply during the entire period of operation.
3. Conditions:
Height over sea level
up to 1000 m
Temperature for temperate climates
from −45°С to +40°С
Relative humidity
no more than 80% when +25°C
4. Working resource:
Operating mode
long
Warranty period
3 years
Full life
not less than 25 years
1. With a rated voltage of LV — 0,4 kV:
Power | Winding connection | Idling losses, kWt | Loss short circuit, kWt | Short-circuit voltage, % | Idling current, % |
---|---|---|---|---|---|
1000 kVA | Y/Yn-0 | 2,0 | 11,5 | 7,2 | 0,8 |
1600 kVA | Y/Yn-0 | 2,75 | 18,0 | 7,2 | 0,8 |
2. With a rated voltage of LV — 6,3 and 10,5 kV:
Power | Winding connection | Idling losses, kWt | Loss short circuit, kWt | Short-circuit voltage, % | Idling current, % |
---|---|---|---|---|---|
1000 kVA | Y/D-11 | 1,8 | 11,6 | 6,5 | 0,3 |
1600 kVA | Y/D-11 | 2,35 | 16,5 | 6,5 | 0,3 |
2500 kVA | Y/D-11 | 3,0 | 23,5 | 6,5 | 0,3 |
4000 kVA | Y/D-11 | 4,5 | 33,5 | 7,5 | 0,3 |
6300 kVA | Y/D-11 | 5.6 | 46,5 | 7,5 | 0,3 |
1. LV — 0,4 kV. Capacity from 1000 to 1600 kVA:
Power | L | B | H | H1 | H2 | H3 | M | А | К | h | h1 |
---|---|---|---|---|---|---|---|---|---|---|---|
1000 kVA | 2310 | 1270 | 2385 | 1545 | 470 | 350 | 400 | 1070 | 145 | 215 | 210 |
1600 kVA | 2610 | 1285 | 2560 | 1760 | 470 | 425 | 400 | 1070 | 210 | 220 | 220 |
Power | Full weight, kg | Transport weight, kg | Oil, kg |
---|---|---|---|
1000 kVA | 3850 | 3850 | 970 |
1600 kVA | 4800 | 4800 | 1340 |
2. LV — 0,4 kV. Capacity 2500 kVA:
Power | L | B | H | H1 | H2 | H3 | M | А | К | h | h1 |
---|---|---|---|---|---|---|---|---|---|---|---|
2500 kVA | 2450 | 2140 | 2700 | 1910 | 470 | 380 | 400 | 1070 | 145 | 240 | 190 |
Power | Full weight, kg | Transport weight, kg | Oil, kg |
---|---|---|---|
2500 kVA | 7500 | 5835 | 2000 |
3. LV — 6,3 / 10,5 kV. Capacity from 1000 to 1600 kVA:
Power | L | B | H | H1 | H2 | H3 | M | А | К | h | h1 |
---|---|---|---|---|---|---|---|---|---|---|---|
1000 kVA | 2280 | 1220 | 2330 | 1545 | 280 | 470 | 400 | 1070 | 200 | 215 | 210 |
1600 kVA | 2450 | 1250 | 2650 | 1760 | 280 | 470 | 400 | 1070 | 200 | 220 | 235 |
Power | Full weight, kg | Transport weight, kg | Oil, kg |
---|---|---|---|
1000 kVA | 3850 | 3850 | 900 |
1600 kVA | 4800 | 4800 | 1340 |
4. LV — 6,3 / 10,5 kV. Capacity 2500 kVA:
Power | L | B | H | H1 | H2 | H3 | M | А | К | h | h1 |
---|---|---|---|---|---|---|---|---|---|---|---|
2500 kVA | 2450 | 2140 | 2700 | 1860 | 280 | 470 | 400 | 1070 | 200 | 240 | 280 |
Power | Full weight, kg | Transport weight, kg | Oil, kg |
---|---|---|---|
2500 kVA | 7100 | 5835 | 1950 |
5. LV — 6,3 / 10,5 kV. Capacity from 4000 to 6300 kVA:
Power | L | B | H | H1 | H2 | H3 | M | А | К | h | h1 |
---|---|---|---|---|---|---|---|---|---|---|---|
4000 kVA | 2820 | 3280 | 3510 | 2230 | 280 | 725 | 400 | 1594 | 240 | 245 | 285 |
6300 kVA | 3000 | 3290 | 3800 | 2505 | 280 | 725 | 400 | 1594 | 240 | 260 | 310 |
Power | Full weight, kg | Transport weight, kg | Oil, kg |
---|---|---|---|
4000 kVA | 9750 | 6920 | 2360 |
6300 kVA | 12000 | 8610 | 2750 |
Download